Setup, Optional controlnet communication – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual
Page 183

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013
183
Communication
Chapter 9
Setup
Setup parameters for the optional DeviceNet port are found in the
Configuration.OptionalComm.DNT
table.
Mac ID
Selects the DeviceNet node address. The range is 0…63 (default).
Communication Rate
Selects the DeviceNet network communication (data) rate, and must be selected
to match the remaining devices on the network. The selections are the following:
•
0 = 125 Kbps
•
1 = 250 Kbps
•
2 = 500 Kbps
•
3 = Autobaud
Optional ControlNet
Communication
PowerMonitor 5000 units can be optionally equipped with a ControlNet
communication port. A ControlNet communication port can be factory
installed or field installed by you. The ControlNet network is an open-standard,
multi-vendor, industrial device data network that supports scheduled, I/O
communication as well as unscheduled messaging. The ControlNet port and the
native Ethernet port can be used simultaneously.
Setup
The
Configuration.OptionalComm.CNT
table contains the Address tag, the
only setup parameter. Valid ControlNet addresses range from 1…99. The default
value is 255.