Install the PowerMonitor 5000 Unit
Chapter 2
Figure 15 - Diagram I3 - 3-phase, 3- or 4-wire, 3 CTs
Status Inputs
Up to four dry (non-powered) contacts can be connected to the
PowerMonitor 5000 unit status inputs. The status input derives 24V DC power
from its internal power supply.
Connect status inputs by using shielded, twisted-pair cable with the shield
connected to the ground bus or other low-impedance earth ground at the contact
end only. The diagram indicates typical status input wiring.
Figure 16 - Status Inputs
L1
L2
L3
Line
CTs (by user)
CT1
CT2
CT3
CT4
(if
used)
Load
Ground
Shorting Terminal
Block (by user)
Metering_Mode = Wye, Delta 3 CT, Open Delta 3 CT,
Delta Grd B Ph 3 CT, or Delta High-leg, as applicable
PowerMonitor 5000
I1
I2
I3
I4
X1
X1
X1
X1
N
(if used)
S1
S2
S3
S4
Scom
Scom
Ground
Ground
Contact 1
Contact 2
Contact 3
Contact 4
PowerMonitor 5000