7
Int16
Event 1 Severity
Severity data for Events 1…6:
0x00 = Minor, recoverable
0x10 = Minor, unrecoverable
0x20 = Major, recoverable
0x30 = Major, unrecoverable
-
0x00…0x30
8
Int16
Event 1 Code
Event code for Events 1…6:
10h Generic Error
20h Current
21h Current, device input side
22h Current, inside the device
23h Current, device output side
30h Voltage
31h Mains Voltage -
32h Voltage inside the device
33h Output Voltage
40h Temperature
41h Ambient Temperature
42h Device Temperature
50h Device Hardware
60h Device Software
61h Internal Software
62h User Software
63h Data Set -
70h Additional Modules
80h Monitoring
81h Communication
82h Protocol Error
90h External Error
F0h Additional Functions
-
0x10…0xF0
9
Int16
Event 2 Severity
-
0x00…0x30
10
Int16
Event 2 Code
-
0x10…0xF0
11
Int16
Event 3 Severity
-
0x00…0x30
12
Int16
Event 3 Code
-
0x10…0xF0
13
Int16
Event 4 Severity
-
0x00…0x30
14
Int16
Event 4 Code
-
0x10…0xF0
15
Int16
Event 5 Severity
-
0x00…0x30
16
Int16
Event 5 Code
-
0x10…0xF0
17
Int16
Event 6 Severity
-
0x00…0x30
18
Int16
Event 6 Code
-
0x10…0xF0
19 … 29
Int16
Reserved
Future Use
0
0
Table 118 - Status.OptionalComm Data Table
Element
Number
Type
Tag Name
Description
Units
Range