Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual
Page 368

368
Rockwell Automation Publication 1426-UM001F-EN-P - November 2013
Appendix B
Technical Specifications
Table 193 - Input and Output Ratings
Parameter
Rating
Voltage Sense Inputs: V1, V2, V3, VN
Input Impedance: 5M ohm min
Input current: 1 mA max
Current Sense Inputs: I1, I2, I3, I4
Overload Withstand: 22 A Continuous, 200 A for one
second
Burden: Negligible
Impedance: Negligible
Maximum Crest Factor at 5 A is 4.0
Starting Current: 5 mA
Status Inputs
Contact Closure (Internal 24V DC)
KYZ Output
Solid State KYZ: 80 mA at 240V AC/V DC
Control Relay
ANSI C37.90 trip duty: 2005
Table 194 - Control Relay
Rating
50/60 Hz AC RMS
DC
Max Resistive Load Switching
10 A at 240V
(2400VA)
10 A at 24V and
0.25 A at 125V
Min Load Switching
100 mA at 5V
10 mA at 5V
UL 508, CSA 22.2, IC Rating Class
B300
Q300
Max Make Values (Inductive Load)
30 A at 120V
15 A at 240V (3600VA)
0.55 A at 125V
0.27 A at 240V (69VA)
Max Break Values (Inductive Load)
3 A at 120V
1.5 A at 240V (360VA)
0.55 A at 125V
0.27 A at 240V (69VA)
Max Motor Load Switching
1/3 HP at 125V
1/2 HP at 240V