Setpoint and logic gate status, Setpoint and logic gate statistics, Commands – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual
Page 168

168
Rockwell Automation Publication 1426-UM001F-EN-P - November 2013
Chapter 7
Logic Functions
Setpoint and Logic Gate Status
Setpoint status is reported in the following tags, found in the
table.
Setpoints_1_10_Active
Bit 0 = Setpoint1_Active (0 = False, 1 = True)
Bit 1 = Setpoint2_Active
…
Bit 9 = Setpoint10_Active
Setpoints_11_20_Active (M6 model)
Bit 0 = Setpoint11_Active (0 = False, 1 = True)
Bit 1 = Setpoint12_Active
…
Bit 9 = Setpoint20_Active
Logic_Level_1 Gates_Active
Bit 0 = Level1_Gate1_Active (0 = False, 1 = True)
Bit 1 = Level1_Gate2_Active
…
Bit 9 = Level1_Gate10_Active
Setpoint and Logic Gate Statistics
Setpoint statistics are reported in the
table, which
includes the following information tags for each setpoint.
Setpoint n Seconds Accumulator
Setpoint n Minutes Accumulator
Setpoint n Hours Accumulator
Setpoint n Transitions to Active x1
Setpoint n Transitions to Active x1000
Logic gate statistics are reported in the
Statistics.Setpoint_Logic Data Table
,
which reports the information listed above for each logic gate (M6 model).
Commands
The following command parameters are found in the
table.