Status – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual
Page 156

156
Rockwell Automation Publication 1426-UM001F-EN-P - November 2013
Chapter 7
Logic Functions
Log_Status_Input_Changes
These are the choices:
0 = Disable recording of status input changes into the status log
1 = Enable recording of event input changes into the status log
Status_Input_1_Input_Scale
Status_Input_2_Input_Scale
Status_Input_3_Input_Scale
Status_Input_4_Input_Scale
When a status pulse is received the count is increased by the scale factor. (Input
pulse * input scale) added to total status count.
Setup for demand EOI synchronization is described in
.
Status
Status input status is reported by the state of the following Boolean tags, found in
the
table. For each tag, 0 = false, 1 = true.
Status_Input_1_Actuated
Status_Input_2_Actuated
Status_Input_3_Actuated
Status_Input_4_Actuated
The scaled value of status input counters are reported in the following tags, found
in the
table.
Status_1_Count_xM
Status_1_Count_x1
Status_2_Count_xM
Status_2_Count_x1
Status_3_Count_xM
Status_3_Count_x1
Status_4_Count_xM
Status_4_Count_x1
These are the semantics:
X 1 = value time 1, range = 0…99,999
X M = value time 1 million, range = 0…9,999,999
Combined range (X M, X 1) = 0…9,999,999,999,999