Power metering – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual
Page 67

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013
67
Metering
Chapter 4
Power Metering
This function applies to all PowerMonitor 5000 models.
Only total three-phase power results are provided when Direct Delta or Open
Delta wiring modes are selected.
Table 10 - Power Metering Metered Parameters
Parameter
Description
Range
Units
L1_kW
Power of individual phase or sum of phases;
signed to show direction
-9.999E15…9.999E15
kW
L2_kW
L3_kW
Total_kW
L1_kVAR
Reactive power of individual phase or sum of
all phases; signed to show direction
-9.999E15…9.999E15
kVAR
L2_kVAR
L3_kVAR
Total_kVAR
L1_kVA
Apparent power of individual phase or sum of
all phases
0…9.999E15
kVA
L2_kVA
L3_kVA
Total_kVA
L1_True_PF_%
The ratio between power and apparent power
for individual phase or all phases
0.00…100.00
%
L2_True_PF_%
L3_True_PF_%
Avg_True_PF
L1_Disp_PF
The cosine of the phase angle between the
fundamental voltage and current for an
individual phase or all phases
0.00…100.00
%
L2_Disp_PF
L3_Disp_PF
Avg_Disp_PF
L1_PF_Lead_Lag_Indicator
Lead or lag indicator for power factor
1 = leading
-1 = lagging
-1…1
±
L2_PF_Lead_Lag_Indicator
L3_PF_Lead_Lag_Indicator
Total_PF_Lead_Lag_Indicator