Setup
Chapter 3
Optional DeviceNet Communication Setup
Choose the Configuration folder and choose the OptionalComm page, which
lets you set the address and communication rate to operate in your system. The
range for DeviceNet_Address is 0…63 (default). The selections for
DeviceNet_Baudrate are the following:
•
0 = 125 Kbps (default)
•
1 = 250 Kbps
•
2 = 500 Kbps
•
3 = Autobaud
Optional DeviceNet Communication on page 182
for more
information on optional DeviceNet communication parameters.
Optional ControlNet Communication Setup
Choose the Configuration folder and then choose the OptionalComm page. The
ControlNet address is the only configurable parameter. The default is 255.
Set Up Date and Time
Follow these steps to set the date and time.
1.
Choose the Configuration folder and choose the DateTime page.
2.
Enter the year, month, day, hour, and minute into the corresponding input
fields and click Apply Changes.
If your power monitor is set up for time synchronization with either a
SNTP or IEEE 1588 PTP server, the time is already set.
IMPORTANT
You can also set up or change the DeviceNet port parameters by using
RSNetWorx for DeviceNet software or similar utilities.