Loggingresults.alarm_log – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual
Page 341

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013
341
PowerMonitor 5000 Unit Data Tables
Appendix A
LoggingResults.Alarm_Log
Table 153 - Table Properties
CIP Instance Number
856
PCCC File Number
N65
No. of Elements
7
Length in Words
7
Data Type
Int16
Data Access
Read Only
Table 154 - LoggingResults.Alarm_Log Data Table
Element
Number
Type
Tag Name
Description
Unit
Range
0
Int16
Alarm_Record_Identifier
Used to verify record sequence when returning multiple records.
1…100
1
Int16
Alarm_Timestamp_Year
The year when the record was recorded.
YYYY
2010…2100
2
Int16
Alarm_Timestamp_Mth_Day
The month and day when the record was recorded.
MMDD
11…1231
3
Int16
Alarm_Timestamp_Hr_Min
The hour and minute when the record was recorded.
HHMM
0…2359
4
Int16
Alarm_Timestamp_Sec_ms
The seconds and milliseconds when the record was recorded.
SSms
0…59,999
5
Int16
Alarm Type
Indicates the type of event that has occurred.
0…512
6
Int16
Alarm Code
Indicates information about the alarm.
0…4096