Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual
Page 195

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013
195
Communication
Chapter 9
Control Block
Select an available Integer word. This example uses N7:0.
Click Setup Screen.
This Controller Data Table Address
For a Read message, the controller tag in which to store the power monitor data.
For a Write message, the controller tag that stores the value written to the power
monitor.
Size in Elements
This is the number of elements being read or written. These are the values:
1 = Single element read or write
2…59 = Multiple element read or write, number of elements to read
including the first element
Channel
Select 1.
Target Device Data Table Address
Look up the PCCC address (in
) of the specific data table address to
read or write. If you are performing a multiple element read or write, this is the
first element in the array.
IMPORTANT
The maximum size in elements is 59 for a 500CPU target device Read type
message.