Loggingresults.event_log – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual
Page 342

342
Rockwell Automation Publication 1426-UM001F-EN-P - November 2013
Appendix A
PowerMonitor 5000 Unit Data Tables
LoggingResults.Event_Log
Table 155 - Table Properties
CIP Instance Number
857
PCCC File Number
N66
No. of Elements
9
Length in Words
9
Data Type
Int16
Data Access
Read Only
Table 156 - LoggingResults.Event_Log Data Table
Element
Number
Type
Tag Name
Description
Unit
Range
0
Int16
Event_Record_Identifier
Used to verify record sequence when returning multiple records.
0…19
1
Int16
Event_Timestamp_Year
The year when the record was recorded.
YYYY
2010…2100
2
Int16
Event_Timestamp_Mth_Day
The month and day when the record was recorded.
MMDD
11…1231
3
Int16
Event_Timestamp_Hr_Min
The hour and minute when the record was recorded.
HHMM
0…2359
4
Int16
Event_Timestamp_Sec_ms
The seconds and milliseconds when the record was recorded.
SSms
0…59,999
5
Int16
Event Type
Indicates the type of event that has occurred.
0…512
6
Int16
General Code
Indicates general information about the status event.
0…4096
7
Int16
Information Code
Indicates specific information about the status event.
0…256
8
Int16
Reserved
Reserved
0