Chapter 6
Logging
Setup
The Min/Max Log requires the following to be configured:
•
Basic metering setup
•
Logging configuration
•
Date and Time setup
Commands
•
Clear single min/max log record
•
Clear min/max log
Related Functions
•
Demand metering
•
Voltage, current and frequency metering
•
Power metering
•
Configuration lock
Load Factor Log
The PowerMonitor 5000 unit maintains a 12-month record of real, reactive and
apparent demand and load factor. Load factor is defined as average demand
divided by peak demand and is a measure of load variability.
Load Factor Log Results
Load factor log records can be retrieved from the PowerMonitor 5000 web page
or ftp server. The power monitor generates the log file at the time of the request.
Records can also be retrieved individually or sequentially by using the data table
interface.
File Name
The log file is named Load_Factor_Log.csv.