Configuration.harmonics_optional_read – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual
Page 288

288
Rockwell Automation Publication 1426-UM001F-EN-P - November 2013
Appendix A
PowerMonitor 5000 Unit Data Tables
Configuration.Harmonics_Optional_Read
Table 93 - Table Properties
CIP Instance Number
819
PCCC File Number
N28
No. of Elements
15
Length in Words
15
Data Type
Int16
Data Access
Write
Table 94 - Configuration.Harmonics_Optional_Read Data Table
Element Number
Type
Tag Name
Description
Default
Range
0
Int16
Channel Selection
Selects the channel associated with the data returned in a
subsequent read of Table PowerQuality.Harmonics_Results.
0 = No Selection
1 = V1-N RMS,
2 = V2-N RMS
3 = V3-N,
4 = VN-G RMS
5 = V1-V2 RMS,
6 = V2-V3 RMS
7 = V3-V1 RMS
8 = I1 RMS
9 = I2 RMS
10 = I3 RMS
11 = I4 RMS
12 = L1 kW RMS
13 = L2 kW RMS
14 = L3 kW RMS
15 = L1 kVAR RMS
16 = L2 kVAR RMS
17 = L3 kVAR RMS
18 = L1 kVA RMS
19 = L2 kVA RMS
20 = L3 kVA RMS
21 = Total kW RMS
22 = Total kVAR RMS
23 = Total kVA RMS
24 = V1-N Angle
25 = V2-N Angle
26 = V3-N Angle
27 = VN-G Angle
28 = V1-V2 Angle
29 = V2-V3 Angle
30 = V3-V1 Angle
31 = I1 Angle
32 = I2 Angle
33 = I3 Angle
34 = I4 Angle
0
0…34
1
Int16
Harmonics Order
Range Selection
Selects harmonics order range. 1 = DC to 31st, 2 = 32nd to 63rd.
1
1…2 (M6)
2…14
Int16
Reserved
Reserved for future use.
0
0