Rockwell Automation 1771-OFE/B Analog Output Module User Manual User Manual
Page 19
Advertising
![background image](/manuals/579097/19/background.png)
2-5
Publication 1771Ć6.5.30 - November 1998
Figure 2.1
LAST STATE Configuration Jumper
Last State Output Level
Configuration Jumpers
MIN
MID
MAX
Front of Circuit Board
HOLD LAST STATE
Table 2.A lists the output ranges and their minimum, maximum, and
middle values.
Table 2.A
Output Last State Configuration Values
Output Range
Selection
Minimum
Value
Middle Value
Maximum
Value
4Ć20mA
4mA
12mA
20mA
0Ć50mA
0mA
25mA
50mA
1Ć5V
1V
3V
5V
0Ć10V
0V
5V
10V
+10V
Ć10V
0V
+10V
These output conditions are active only if the following conditions
exist:
•
the module faults
•
the processor is in the PROGRAM or TEST mode
•
rack switch 1 is in the reset position
Advertising