Rockwell Automation 1771-OFE/B Analog Output Module User Manual User Manual

Page 59

Advertising
background image

MAX

Front
of
Mod-
ule

Printed Circuit Board

TopView

Mid

Max

Hold last state

Min

Position plugs as required.

11919ĆI

MAX

MIN

6-7

Publication 1771Ć6.5.30 - November 1998

4. Place the LAST STATE configuration jumpers (Figure 6.5) in the

MAX position (if they are not there already).

Figure 6.5

LAST STATE Configuration Jumpers in MAX Position

LAST STATE

5. Connect the voltmeter leads across the top two screws on the field

wiring arm (Channel 1). The top screw is positive, and the
second (lower) screw is negative.

6. Turn on the processor, I/O chassis, and the industrial terminal.

7. Place the processor in the TEST or PROG mode.

8. Output full scale (+20mA) either with write block transfer data or

by placing the LAST STATE configuration jumpers in the MAX
position.

9. Adjust R66 until the reading is +5V (20mA) +2mV (Figure 6.6).

10.Output +4mA (1V - minimum scale) either with write block

transfer data or by placing the LAST STATE configuration
jumpers in the MIN position.

11. Adjust R67 until the reading is 3/4 the difference between 1V and

the initial minimum scale reading.