Rockwell Automation 1771-OFE/B Analog Output Module User Manual User Manual

Page 20

Advertising
background image

2-6

Publication 1771Ć6.5.30 - November 1998

Rack switch 1 determines what output conditions occur during a rack
fault.

Rack Switch 1

S tti

Configuration Jumper Setting

Setting

MIN

MID

MAX

HOLD LAST STATE

Last State

Last State

Last State Last State

Last State

Reset

Min

Mid

Max

Last State

To set the last state configuration jumpers, proceed as follows.

!

ATTENTION: Do not insert modules into or remove
modules from the I/O chassis while system power is
ON. Failure to observe this rule could result in damage
to module circuitry and unexpected machine operation.

1. Locate the jumpers as shown in Figure 2.1.

2. Carefully pull up on the jumpers to remove from the pins.

3. Reposition as necessary to provide the value selected in

Table 2.A.

Setting Voltage Range Configuration Jumpers (1771ĆOFE1 only)

If you ordered the voltage output version, you must set several
configuration jumpers located inside the module on the circuit board.
To do this, follow these steps:

2. Locate the configuration jumpers and set them according to your

output voltage requirements (Figure 2.3).

Last State Output Level

Configuration Jumpers

Access holes for

Configuration

Jumpers

5. Position the jumpers as indicated in Figure 2.3.