Chapter

3

Publication 1771Ć6.5.30 - November 1998

Configuring Your Output

Module

In this chapter, you will read about:

For information on

See page

Configuring Your Module . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Configuration Word . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Default Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Data Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Scaling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
Procedure for Configuring Your Module . . . . . . . . . . . . . . . . . 3-9

Because of the many analog devices available and the wide variety
of possible applications, you must configure the module to conform
to the analog device and specific application that you have chosen.
You do this with a block transfer write instruction (BTW). The write
block can be up to 13 words long and contains output data and
information on data format and scaling.

Word Assignment for Block Transfer Write

Word/Dec. Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Word/Octal Bit

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

1

Channel 1 Data Value

2

Channel 2 Data Value

3

Channel 3 Data Value

4

Channel 4 Data Value

5

Data Format

Reserved

Minimum/Maximum ScalingValue Polarity

Data Polarity

6

Channel 1 Minimum ScalingValue

7

Channel 1 Maximum ScalingValue

8

Channel 2 Minimum ScalingValue

9

Channel 2 Maximum ScalingValue

10

Channel 3 Minimum ScalingValue

11

Channel 3 Maximum ScalingValue

12

Channel 4 Minimum ScalingValue

13

Channel 4 Maximum ScalingValue

Important: A block transfer write length of 0 will result in a default

length of 13. A block transfer read length of 0 will
result in a default length of 5.

What This Chapter

Contains

Configuring Your Module