Rockwell Automation 1771-OFE/B Analog Output Module User Manual User Manual

Page 73

Advertising
background image

B-3

Publication 1771Ć6.5.30 - November 1998

The output module is capable of transferring up to 13 words in one
program scan. The number of words transferred is determined by the
block length entered in the output image table control byte.

The bits in the output image table control byte (Bits 00-05) must be
programmed to specify a binary value equal to the number of words
to be transferred.

For example, Figure B.2 shows if your output module is set up to
transfer five words, you would set Bits 00 and 02 of the lower output
image table control byte. The binary equivalent of five words, as
stated in the look-up table, is 000101.

Figure B.2

Setting Block Length

Data Address

Contains Module

Address in BCD

Output Image Table Control

Byte Contains Read

Enable Bit andBlock

Length in Binary Code

010

012

017

027
030

1

2

0

Data Table

1
R

Control

Byte

Read5 Words

from Module

Block Transfer

ReadEnable Bit

For Block

Transfer Active

Operations Only

Output Image Table

12995

1 0 0 0 0 1 0 1

Binary Bit Pattern

Lower Output Image Table Byte

05

04

03

02

01

00

0

0

0

0

0

0

Default

0

0

0

0

0

1

1

0

0

0

0

1

0

2

0

0

0

0

1

1

3

0

0

0

1

0

0

4

0

0

0

1

0

1

5

0

0

0

1

1

0

6

0

0

1

1

0

1

13

Number of

Words

to Transfer

Setting the Block Length

(Multiple GET Instructions

Only)

Advertising