Rungs 2 and 3
These OUTPUT ENERGIZE instructions (012/01 and 012/02)
define the number of words to be transferred. This is accomplished
by setting a binary bit pattern in the module’s output image table
control byte. The binary bit pattern used (Bits 01 and 02 energized)
is equivalent to six words or channels and is expressed as 110 in
binary notation.
Rung Summary
Once the block transfer read operation is complete, the processor
automatically sets Bit 07 in the input image table status byte and
stores the block length of the data transferred.