Rockwell Automation 1771-OFE/B Analog Output Module User Manual User Manual

Page 45

Advertising
background image

4-9

Publication 1771Ć6.5.30 - November 1998

Figure 4.6

PLCĆ5 Example Program 1

N10:0

15

BTW

BLOCK XFER WRITE

Rack Address:

Group Address:

Module Address:

Control Block:

0

0

0

N10:0

Data File:

Length:

N10:5

13

EN

DN

ER

Continuous:

N

1

Rung 1

The BTW is writing in an

asĆfastĆasĆpossible" mode. As soon as

the instruction executes, it is reenabled for

another transfer. Instruction execution

could also be scheduled using a timer

done bit or some other input condition.

Program Action (Example 1)

Module Location

Rack 0, Module Group 0, Slot 0

File Configuration

Control Array

N10:0

Data File

N10:5

Configuration Word

N10:9

Enable Bit

N10:0/15

Figure 4.7

PLCĆ5 Example Program 2

N10:0

15

BTR

BLOCK XFER READ

Rack Address:

Group Address:

Module Address:

Control Block:

0

0

0

N11:0

Data File:

Length:

N11:5

5

EN

DN

ER

Continuous:

N

N11:0

15

N10:0

15

BTW

BLOCK XFER WRITE

Rack Address:

Group Address:

Module Address:

Control Block:

0

0

0

N10:0

Data File:

Length:

N10:5

13

EN

DN

ER

Continuous:

N

N11:0

15

1

2

Program Action (Example 2)

Rung 1

The enable bits of both instructions

alternate execution between rungs.

This rung is executed first. When the

BTR is done, both enable bits are off

until the next rung is scanned at which

time the BTW is enabled.
Rung 2

The BTW is writing in an

asĆfastĆasĆpossible" mode. As soon as

the instruction executes, it is reenabled for

another transfer. Instruction execution

could also be scheduled using a timer

done bit or some other input condition.

Module Location

Rack 0, Group 0, Slot 0

File Configuration

BTR

Control Array

N11:0

Data File

N11:5

Output Data Image

N11:5 through N11:8

Status Word

N11:9

Enable Bit

N11:0/15

File Configuration

BTW

Control Array

N10:0

Data File

N10:5

Configuration Word

N10:9

Enable Bit

N10:0/15