Rockwell Automation 1771-OFE/B Analog Output Module User Manual User Manual

Page 34

Advertising
background image

3-8

Publication 1771Ć6.5.30 - November 1998

If you do not wish to scale a particular channel, set the scaling values
as shown below.

If your range is:

Set Maximum

Scaling Value to:

Set Minimum

Scaling Value to:

4Ć20mA

1Ć5V

4095

0000

0Ć10V

+10 to Ć10V

4095

Ć4095

1

1

This also requires you to set the appropriate sign bit in the configuration word for the minimum

scaling value.

For example, suppose you choose the 1 to 5 volt range and BCD
data format for your module. You have a thermocouple input that
reports a temperature between 100

o

C and 900

o

C back to your

processor. You would like this input temperature scale to correspond
to an output meter scale.

You would enter the following minimum and maximum scaling
values into Words 6 and 7 of the write block:

Meter Scale Value

Scaled Value

Output Voltage

Unscaled

Value (BCD)

Meterscale 100%

900

o

C

5.0V

4095

700

o

C

4.0V

3072

Example:

Word 6 = 0100

Word 7 = 0900

500

o

C

3.0V

2048

Example:

Meterscale 31%

Meterscale 25%

350

o

C

300

o

C

2.25V

2.0V

1280

1024

Meterscale 0%

100

o

C

1.0V

0

If the processor sends a data value to the module that corresponds to
350

o

C, the value is scaled to the 100

o

C to 900

o

C range and the

corresponding output voltage for that channel is 2.25 volts, which
would position the scale accordingly at 31% of full scale.