Scaling is the conversion of unscaled data to engineering units--such
as gallons/minute, degrees centigrade, and pounds/square inch. You
can use the scaling feature to send the data for each channel to the
module in an optional scaled value representing actual engineering
units. This value is scaled by the module to a proportional binary
value before it is used by the corresponding channel. The resolution
of this data is one part in 4095.

The scaling feature is implemented by entering scaling values in the
data format selected in words 6 through 13 of the BTW.

ScalingValue Polarity

Bits 04 to 11 (04 to 13 octal) of the configuration word (word 5) in
the write block designate positive or negative scaling values
(Figure 3.2). By setting the appropriate negative scaling bit in word
5, you can scale negative data or enable a negative scaling value.
The sign bits are ignored if a corresponding channel is not scaled.

Figure 3.2

Location of ScalingValue Polarity Bits in the Block Transfer Write

Configuration Word

Word/Dec. Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Word/Octal Bit

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

Word 5

4

4

3

3

2

2

1

1

4

3

2

1

Data Format

Reserved

1 = Binary

0 = BCD

Maximum Scaling Value Polarity

1 = Negative
0 = Positive

Minimum Scaling Value Polarity

1 = Negative
0 = Positive

Data Sign Polarity

1 = Negative

0 = Positive

4 = Channel 4

3 = Channel 3

2 = Channel 2

1 = Channel 1

12883

Maximum and Minimum ScalingValues

Words 6-13 of the write block transfer contain maximum and
minimum scaling values for each channel. Word 6 corresponds to
Channel 1 scale minimum, word 7 to Channel 1 scale maximum,
word 8 to Channel 2 scale minimum, and so on (Figure 3.3).

The maximum and minimum scaling values are the upper and lower
limits for output data. The module’s microprocessor reads these
values and automatically scales output data from the write block
transfer.