Rockwell Automation 1771-OFE/B Analog Output Module User Manual User Manual

Page 42

Advertising
background image

0

1

0

0

Channel 3 Minimum Scaling Factor Polarity

Set (1) = Negative

Reset (0) = Positive

Binary

BCD

12892

4-6

Publication 1771Ć6.5.30 - November 1998

Figure 4.3

Binary Configuration Word Represented in BCD

Word/Dec. Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Word/Octal Bit

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

Word 5

0

0

0

0

0

0

0

1

0

0

0

0

0

0

0

0

Block transfer operation with the PLC-3 processor uses one binary
file in a data table section for module location and other related data.
This is the block transfer control file. The block transfer data file
stores data that you want transferred to your module (during block
transfer write) or from your module (block transfer read). The
address of the block transfer data file is stored in the block transfer
control file. A sample program segment is shown in Figure 4.4 and
described in the following paragraphs.

The industrial terminal prompts you to create a control file when
either block transfer instruction is entered. The same block transfer
control file is used for both read and write instructions for your
module.

PLC-3 Example Program

Module Location

Rack 1, Module Group 0, Slot 1

Block Transfer Control File

FB1:0

BTW File (Configuration file)

FB2:1

BTR File (Buffer file)

FB3:1

Output Data File

FB4:1

Storage Bit

B0/0

BTW Done Bit

B1:0/05

BTR Done Bit

B1:0/15

Module Configuration

1771ĆOFE1 (Voltage Version)

Voltage Range

1 to 5V

Data Format

BCD

Scaling Parameters

Channels 1 and 2 = No scaling

Channel 3 = Ć20 to 275

Channel 4 = 100 to 500

Block Transfer

Programming Ć PLCĆ3

Family Processors Only

Advertising