European Hazardous Location Approval

The following applies when the product bears the

marking.

This equipment is intended for use in potentially explosive atmospheres as
defined by European Union Directive 94/9/EC and has been found to comply
with the Essential Health and Safety Requirements relating to the design and
construction of Category 3 equipment intended for use in Zone 2 potentially
explosive atmospheres, given in Annex II to this Directive.

Compliance with the Essential Health and Safety Requirements has been assured
by compliance with EN 60079-15 and EN 60079-0.

ATTENTION: This equipment is not resistant to sunlight or other sources of UV
radiation.

WARNING: This equipment shall be mounted in an ATEX-certified enclosure
with a minimum ingress protection rating of at least IP54 ( as defined in
IEC60529) and used in an environment of not more than Pollution Degree 2 (as
defined in IEC 60664-1) when applied in Zone 2 environments. The enclosure
must have a tool-removable cover or door.

WARNING: This equipment shall be used within its specified ratings defined by
Rockwell Automation.

WARNING: Should the unit be installed in an environment where induced
transients could exceed 44V, then external transient/surge arrestors should be
installed.

WARNING: Secure any external connections that mate to this equipment by
using screws, sliding latches, threaded connectors, or other means provided
with this product.

WARNING: Do not disconnect equipment unless power has been removed or
the area is known to be nonhazardous.

WARNING: Devices shall be used in an environment of not more than Pollution
Degree 2.