Field device page – Rockwell Automation 1788-EN2PAR EtherNet/IP and ControlNet to PROFIBUS PA Linking Device User Manual User Manual

Page 59

Advertising
background image

Rockwell Automation Publication 1788-UM058B-EN-P - September 2014

59

Linking Device Display Status

Appendix A

Field Device Page

The next 23 Field Device pages
display the status of each of the
field device indices.

PANode

: Displays the PA node

address.

Ident

: Displays the ident (identity)

number of the specific field device.

Status:

Displays the field device

status (see

Table 9

).

Table 9 - Field Device Status Descriptions

Success

:

Displays the data packets that are received as a percentage of packets

that are sent for the previous 100 packets.

Pckt Send

:

Displays the total number of data packets that are sent from the field

device.

Pckt Recv

:

Displays the total number of data packets that are received from the

field device.

Bad CRC

:

Displays the total number of bad CRC packets received.

No Reply

:

Displays the total number of data requests to which the field device

did not respond.

Status Message

Description

Not Connected

The device cannot be seen.

Online

The device is online but not configured.

ConfigRunning

The device is configured and exchanging data.

N/A

The device has not been added to the configuration.