Rockwell Automation 1788-EN2PAR EtherNet/IP and ControlNet to PROFIBUS PA Linking Device User Manual User Manual

Page 47

Advertising
background image

Rockwell Automation Publication 1788-UM058B-EN-P - September 2014

47

Logix Assemblies

Chapter 3

ParameterFault

This bit is set if there is a fault in the parameterization of the field device.

ParameterReq

This bit is set if the device has not received its parameterization.

FreezeMode

This bit is set if you enable Freeze mode in the parameterization of the field
device and a global control is sent to freeze the device PVs.

SyncMode

This bit is set if you enable Sync mode in the parameterization of the field device
and a global control is sent to synchronize the device PVs.

WatchDog

This bit is set if the watchdog is enabled in the parameterization of the field
device.

PAIdent

This is the identity number of the specific field device.

PVReal1…PVReal8

If you set a process variable to be a Real format, the data is displayed in this
section.

PVStatus1…PVStatus8

If you set a process variable to have a Status, the status value for the each PV is
displayed in this section.

See the user manual of the field device for the definition
of the PV status. In general, the status definitions are as
follows:

Good = a value

≥ 0x80

Uncertain = a value from 0x40…0x7F

Bad = a value

< 0x40 (for example, 0…0x3F)

PVInt1…PVInt8

If you set a process variable to be a 1-byte to 4-byte format, the data is displayed in
this image.