North american hazardous location approval – Rockwell Automation 1788-EN2PAR EtherNet/IP and ControlNet to PROFIBUS PA Linking Device User Manual User Manual

Page 13

Advertising
background image

Rockwell Automation Publication 1788-UM058B-EN-P - September 2014

13

Preface

North American Hazardous Location Approval

The following information applies when operating this equipment in hazardous
locations.

The following information applies when operating this equipment
in hazardous locations:

Informations sur l'utilisation de cet équipement
en environnements dangereux:

Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division
2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each
product is supplied with markings on the rating nameplate indicating the
hazardous location temperature code. When combining products within a
system, the most adverse temperature code (lowest "T" number) may be used to
help determine the overall temperature code of the system. Combinations of
equipment in your system are subject to investigation by the local Authority
Having Jurisdiction at the time of installation

Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu'à une
utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux
et non dangereux. Chaque produit est livré avec des marquages sur sa plaque
d'identification qui indiquent le code de température pour les environnements
dangereux. Lorsque plusieurs produits sont combinés dans un système, le code
de température le plus défavorable (code de température le plus faible) peut
être utilisé pour déterminer le code de température global du système. Les
combinaisons d'équipements dans le système sont sujettes à inspection par les
autorités locales qualifiées au moment de l'installation.

WARNING: EXPLOSION HAZARD

Do not disconnect equipment unless power has

been removed or the area is known to be
nonhazardous.

Do not disconnect connections to this equipment

unless power has been removed or the area is
known to be nonhazardous. Secure any external
connections that mate to this equipment by using
screws, sliding latches, threaded connectors, or
other means provided with this product.

Substitution of components may impair suitability

for Class I, Division 2.

If this product contains batteries, they must only be

changed in an area known to be nonhazardous

AVERTISSEMENT: RISQUE D'EXPLOSION

Couper le courant ou s'assurer que l'environnement

est classé non dangereux avant de débrancher
l'équipement.

Couper le courant ou s'assurer que l'environnement

est classé non dangereux avant de débrancher les
connecteurs. Fixer tous les connecteurs externes
reliés à cet équipement à l'aide de vis, loquets
coulissants, connecteurs filetés ou autres moyens
fournis avec ce produit.

La substitution de composants peut rendre cet

équipement inadapté à une utilisation en
environnement de Classe I, Division 2.

S'assurer que l'environnement est classé non

dangereux avant de changer les piles.

WARNING: If you connect or disconnect the communications cable with power
applied to this module or any device on the network, an electrical arc can occur.
This could cause an explosion in hazardous location installations. Be sure that
power is removed or the area is nonhazardous before proceeding.

WARNING: Temperature rating of conductors must be
higher than 82 °C (179.6 °F).

WARNING: If you connect or disconnect wiring while the field-side power is on,
an electrical arc can occur. This could cause an explosion in hazardous location
installations. Be sure that power is removed or the area is nonhazardous before
proceeding.

Advertising