The lower portion of the main page shows the communication quality to each
field device represented as a percentage of data packets sent compared to data
packets received for each field device index (see

Table 8

).

Table 8 - Field Device Communication Quality

PA Master Page

The next page that is accessed by
the Page button is the PA Master
page.

Bus A/B:

Displays the bus

voltages and currents.

Temperature:

Displays the

internal temperature of the linking
device.

External Pwr:

Displays the power

supply voltage.

PA Node:

Displays the node

address of the linking device.

Bus A/B Enabled:

PA Bus A and/or PA Bus B is enabled for communication.

Bus A/B Tripped:

PA Bus A and/or PA Bus B has tripped indicating that there

was an over-current on either port.

Bus A/B Term:

The linking device is configured to terminate PA Bus A and/or

PA Bus B.

Display

Communication Quality

>>>

95+

>>

80+

>

70+

X

60+

XX

50+

XXX

Below 50

???

Unknown