Chapter 2

Set Up in the Studio 5000 Logix Designer Application

Download

Downloads the configuration to the linking device. The linking device saves the
configuration in non-volatile memory.

Upload

Uploads the configuration from the linking device to the Studio 5000 Logix
Designer project.

Scan

Finds the field devices on the local PA bus and applies a default configuration to
each device according to the GSD file of the manufacturer. The AOP scans up to
the max scan address (see

Max Scan Address on page 31

).

Add Device

Manually adds a device that is not currently connected. The same default
configuration is applied to the field device that is added.

Copy Device

Copies a field device configuration and applies it to all other locations.

Delete Device

Deletes a device from the tree.

Delete All

Deletes all field devices from the configuration.

IMPORTANT

After the configuration has been downloaded to the linking device, cycle
power for the new configuration to take effect.

IMPORTANT

Click the Apply button in the AOP to save the configuration to the Studio 5000
Logix Designer project.

TIP

If you want to replicate the configuration to many devices, the Copy Device
button can speed up the process.