Ethernet Switch Settings

This table describes the Ethernet switch settings.

ControlNet Switch Settings

The linking device connects to a ControlNet network with a BNC connector.
Set the ControlNet node address with the switches under the front cover.

This example shows a linking device set to the
ControlNet address of 12.

Ethernet Switch Setting

Description

To set the IP address of the linking device to the 192.168.1.xxx sub net, set the
switches to the required last three digits.
In this example, the linking device will start up with IP address: 192.168.1.123.

To set the IP address of the linking device via a BOOTP server, set the switches to
888 (factory default setting).
Power up the linking device and set the IP address by using any BOOTP server.
Once the new IP address has been set, power down the linking device, return the
switches to 000, and power up the linking device.

Normal setting after setting IP address with BOOTP.
The 000 setting disables BOOTP and holds the IP address.

The linking device can run the firmware that it was originally shipped with.
If power was cycled while upgrading the firmware, the linking device could fail to
start because the firmware was corrupted.
Set the switches to 777 to set the linking device into Safe mode and upgrade the
firmware again.