Rockwell Automation Publication 1788-UM058B-EN-P - September 2014

45

Chapter

3

Logix Assemblies

PA Master Input Image

Each linking device uses a total of four connections from the Logix controller,
regardless of the field device count. Therefore, the input and output image of
each linking device is divided into four sections, A through D. Connection A has
the data for the linking device and four field devices. Connections B, C, and D
have the data of four field devices each.

Figure 9

shows the input image of the PA

master.

Figure 9 - PA Master Input Image

Bus A/B Tripped

If too much current is drawn (> 500 mA) on Bus A or Bus B, a trip occurs and the
bus is no longer functional. The trip is indicated in the input image.

NewFieldDevice

This bit is set when a new field device is found that is not in the configuration of
the PA master.

MultiMasterActive

This bit is set after the two PA master modules have synchronized, and they have
the same node number and the same configuration.

MasterMode

This value indicates the currently implemented topology (see

Appendix B

).

IMPORTANT

Both PA Masters must have the same configuration (master and field devices)
for the masters to be able to synchronize.