Linking Device Display Status

The display of the linking device provides status and diagnostic data in one of
three page formats: main page, PA master page, or field device page. Use the Page
button behind the front cover to scroll through the pages (see

Hardware Switches

Location on page 22

for location of the Page button).

Main Page

The main page is the default
display. The linking device returns
to this page after 10 seconds.

PA Bus A/B:

Displays the bus

voltages on each port.

IP:

Displays the current IP address

or BOOTP if enabled.

CNet MAC:

Displays the current

ControlNet node address
(1788-CN2PAR linking device
only).

STS:

Displays the status

(see

Table 7

).

Table 7 - STS Status Descriptions

Status Message

Description

ok

No events.

new device found

A new field device is on the bus.

redundancy ok

Masters are synchronized.

redundancy err

The master linking devices are out of sync.

bus A tripped

PA bus A has tripped because of over current.

bus B tripped

PA bus B has tripped because of over current.

SAFE MODE

The linking device has been set into safe mode.

not owned

No connection to a Logix controller.