Rockwell Automation Publication 1788-UM058B-EN-P - September 2014

Chapter 2

Set Up in the Studio 5000 Logix Designer Application

PROFIBUS PA Redundancy
Setup

The linking device provides PROFIBUS PA and Ethernet architectures. This
section describes the PROFIBUS PA redundancy options that are available, and
highlights the benefits and sets required to implement them.

Hardware

This section describes the hardware redundancy for media and master devices.

Media Redundancy

For media redundancy, you can select from dual trunk or ring redundant media
architecture. When selecting the architecture, select the correct setup in the
linking device AOP. See

Software on page 39

for more details. Here are examples

of dual trunk and ring architectures.

Figure 2 - Dual Trunk Media Redundancy

Figure 3 - Ring Media Redundancy

IMPORTANT

To create the redundant media architecture, use the 1788-PARJB junction box.

IMPORTANT

When using dual trunk redundancy, the total difference in cable length
between trunk cable A and trunk cable B must not exceed 250 m (820 ft). This
applies even when using multiple junction boxes.