Chapter 1

Cable Type and Minimum Requirements

Per section 12.8.2 of IEC61158-2 (Physical Layer Specification), the PROFIBUS
PA cable must meet the following minimum requirements:

Impedance at 31.25 kHz of 100

Ω

± 20%

Maximum attenuation of 3 dB/km

Conductor cross-sectional area of 0.8mm

2

(18 AWG)

Shield coverage of at least 90%

Maximum DC resistance of 24

Ω

/km per conductor

Maximum capacitive unbalanced to the shield of 4nF/km

Cable Color Coding

Per section 12.8.8 of IEC61158-2 (Physical Layer Specification), the color code
of the PROFIBUS PA cable must match the descriptions in the following table.

Termination Guidelines

Terminate the PA bus cable at the beginning and end of the cable. You can set the
linking device to be internally terminated. If the architecture allows it,
terminators can be placed at different locations. See

Appendix B

for architectures

and their correct termination locations.

Verify that junction boxes are not terminated internally. More than two
terminators will cause the communication signal to become slewed and
attenuated, which causes the signal to become unreadable.

Per section 12.8.6 of IEC61158-2 (Physical Layer Specification), terminator
impedance is equal to a 100

Ω

resistor in series with a 1

μ

F capacitor.

Cable Strand

Color

PA cable positive (+)

Red

PA cable negative (-)

Green

Non-IS PA cable

Black

IS PA cable

Blue or blue/black