Install and Wire the Modules 17

Ground the Cable

Signal cable such as Belden cable #8761 (or equivalent) has two signal
wires (black and clear), one drain wire, and a foil shield. The drain
wire and foil shield must be grounded at only one end of the cable,
not at both ends.

Typical Signal Cable

Determine Cable Length

When you determine the length of cable required to connect an I/O
device, remember to include additional length to route the drain wire
and foil shield to earth ground. Route your cable long enough to
avoid areas of high radiated electrical noise, but short enough to avoid
signal attenuation.

IMPORTANT

Ground the cable shield at one end having a good earth-ground
connection, such as at an I/O chassis mounting bolt or nearest
ground bus in the I/O enclosure. Make this connection as short
as possible. Do not ground the cable at the module’s terminal
block.

Insulation

Shrink Wrap

Clear Wire

Drain Wire

Black Wire

Foil Shield