44 Write Ladder Logic

Scale an Analog Input and
Detect an Out-of-range
Condition

The following example shows input range checking and scaling the
analog input to engineering units for a 1746-FIO4V analog input
module.

We are making the following assumptions:

• The 1746-FIO4V module is located in slot 3 of a modular system.
• A pressure sensor with a 0…10V dc output is wired to input

channel 1.

• The sensor signal voltage is proportional to a range of

100…500 PSI.

• The process pressure must stay between 275…300 PSI.

(If the pressure deviates from this range, your logic sets an alarm
bit.)

• Data is presented in PSI for monitoring and display purposes.

Input Scaling

The scaling operation is displayed in the following graph. It displays
the linear relationship between the input and the resulting scaled
values.

Input Scaling

500 PSI
(scaled max)

100 PSI
(scaled min)

300 PSI

275 PSI

Scaled
Value

Input Value

Process operating range

4095 = 10V dc
(input max)

High
Limit

Low
Limit

0 = 0V dc
(input min)