Convert Analog Input Data

The module converts analog input signals to 12-bit binary values for
storage in the input image table.

The decimal range, number of significant bits, and converter
resolution depend on the input range that you use for the channel.

Compute the Analog Input Signal Level

Use the following formula to determine what the analog input signal
level (sensor signal) should be for a given decimal value in the input
image table.

For voltage inputs, a full scale input of 10V dc has a full scale count of
4095 and a full scale input of 5V dc has a full scale count of 2047.

For current inputs, a full scale input of 20 mA has a full scale count of
2047.

Input Range

Decimal Range
(input image table)

Significant
Bits

Nominal Resolution

0…10V – 1LSB

0…4095

12

2.4414 mV/LSB

0…5V

0…2047

11

1…5V

409…2047

10

0…20 mA

0…2047

11

9.7656 µA/LSB

4…20 mA

409…2047

10

Full Scale Input
Full Scale Count

Sensor Signal =

x Input Image Value

Sensor Signal = 2.44 mV/count x Input Image Value

Sensor Signal = 0.00977 mA/count x Input Image Value