Processor and Module Considerations 31

Address I/O Image Words

Each module input channel is addressed as a single word in the
processor’s input image table and each module output channel is
addressed as a single word in the processor’s output image table. The
module uses a total of two input words and two output words.

Processor I/O Image Words Used by the Module

The converted input values from input channels 0 and 1 are addressed
as words 0 and 1 of the slot where the module resides. The output
values for the output channels 0 and 1 are addressed as output words
0 and 1 of the slot where the module resides.

Analog Input
Sensors

Word Addresses
in I/O Image File

Input Channel 0

Input Module’s
A/D Converter

Bit 15

Bit 0

Input 0

Input 1

Input Channel 1

Input
Scan

Output Image

Input Image

I:e.0
I:e.1

O:e.0
O:e.1

e = module’s slot number in I/O rack

Output
Scan

Output Channel 0

Bit 15

Bit 0

Output Channel 1

Analog Output
Devices

Output 0

Output 1

EXAMPLE

You would address the output image word for output O, word 0,
in slot 3 as: O:3.0 where delimiters : and . must be placed as
shown.

O:e.0-4

delimiters

Capital Letter
I = Input, or
O = Output

module’s I/O rack slot location

I/O image table word