Rockwell Automation 1746-FIO4V SLC 500 Fast Analog I/O/ User Manual User Manual

Page 9

Advertising
background image

Publication 1746-UM009B-EN-P - September 2007

Quick Start 9

4. Configure the system I/O and module ID.

With the software, configure the processor, I/O racks, slots, and
I/O modules.

When assigning an I/O module to a slot location, select the
module from the displayed list. If not listed, select OTHER at the
bottom of the list and enter the module’s ID code at the prompt.

ID code for 1746-FIO4I is 3224
ID code for 1746-FIO4V is 3218

5. Understand A/D & D/A converter resolution on input and

output words.

The module’s I/O channel converters limit bit usage to less than
a full 16-bit word.

The input channel converter resolution is 12 bits, where the
highest four bits are always zero.

The output channel converter resolution is 14 bits, where the
lowest two bits are never used.

For Differential Inputs

For Single-ended Input
with 3-wire Transmitter

Analog
Sensor

+

Earth
Ground

Important: Jumper
unused inputs.

Load

Earth
Ground

Important: Do not
jumper unused outputs.

Power
Supply

+

Transmitter

Signal

Supply

GND

3
4
5

Module

IN +
IN –
ANL COM

Module

0
1
2

IN 0 +
IN 0 –
ANL COM

3
4
5

IN 1 +
IN 1 –
ANL COM

6
7
8

Not Used
OUT 0
ANL COM

9

10

11

Not Used
OUT 1
ANL COM

Advertising
This manual is related to the following products: