Write Ladder Logic 51

Ladder Logic

The following ladder logic uses standard math. It unlatches the
mathematical overflow bit S2:5/0 before the end of the scan to
prevent a processor fault. The module is located in slot 2, and the
output device is wired to channel 0.

Scale Offset

] [

GREATER THAN
Source A
Source B

N7:0
100

Rung 2:0
Set in-range bit

Rung 2:1
Check for below range

Rung 2:2
Check for above range

Multiply by the
scaled range

Clear fault bit
from overflow

Add offset

B3/0
(U)

S2:5/0

(U)

LES

GRT

MUL

DDV

ADD

LESS THAN
Source A
Source B

N7:0
0

MULTIPLY
Source A
Source B
Dest

N7:1
3685
N7:1

DOUBLE DIVIDE
Source A
Dest

10
N7:1

ADD
Source A
Source B
Dest

N7:1
205
0:2.0

B3/0
(L)

MOV

MOVE

Source A
Dest

205
0:2.0

B3/0

B3/0
(U)

MOV

MOVE

Source A
Dest

3890
0:2.0

Rung 2:3
Scale the analog input

SUB

SUBTRACT
Source A
Source B
Dest

N7:0
90
N7:1

Subtract the
input minimum.

Divide result
by input range