Scale an analog output, Calculate the linear relationship – Rockwell Automation 1746-FIO4V SLC 500 Fast Analog I/O/ User Manual User Manual

Page 47

Advertising
background image

Publication 1746-UM009B-EN-P - September 2007

Write Ladder Logic 47

Scale an Analog Output

This example shows the scaling of analog output values to
engineering units for monitoring or controlling purposes.

We are making these assumptions.

• The FIO4I module is located in slot 2 of an SLC 500 system.
• An actuator of a flow control valve is wired to output channel 0.
• The actuator accepts a 4…20 mA signal for a 0…100% of valve

opening.

• The actuator can not receive a signal out of the 4…20 mA range.
• The percentage of valve opening is manually input to the SLC

processor.

This graph displays the linear relationship.

Calculate the Linear Relationship

Use these equations to compute the scaled output value:

20mA = 31208
(scaled max.)

4mA = 6242
(scaled min.)

Scaled
Value

Input Value
(from data table)

100%
(input max.)

0%
(input min.)

Scaled value = (input value x slope) + offset

Slope = (scaled range) / (input range)

Offset = scaled min – (input min x slope)

= (scaled max – scaled min) / (input max – input min)

= 6242 – [0 x (24966 / 100)] = 6242

Scaled value = [input value x 24966 / 100] + 6242

= (31208 – 6242) / (100 – 0) = 24966/100

The slope is greater than 3.2767 so you cannot use SCL instruction.

Advertising
This manual is related to the following products: