Processor and Module Considerations 35

EXAMPLE

If the module’s output range is 4…20 mA and you want to set
the output to 4 mA, compute the output image value as follows.

IMPORTANT

The actual resolution for analog current outputs is 2.56348
µA/LSB, where the 14-bit decimal representation is left
justified as follows.

EXAMPLE

Use the following formula to compute the output image value if
the module’s output range is 1…5V dc and you want to set the
output to 1V dc.

IMPORTANT

The actual resolution for analog voltage outputs is 1.22070
mV/LSB, where the 14-bit decimal representation is left
justified as follows.

31,208
20 mA

Output Image Value =

x 4 mA 6242

~

CHANNEL OUTPUT WORD

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Bits not

Isb

msb

16,384
5V dc

Output Image Value =

x 1V dc 3277

~

Channel Output Word

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Bits not used

Isb

msb