Write Ladder Logic 45

Calculate the Linear Relationship

Use the following equations to express the linear relationship between
the input value and the resulting scaled value.

Calculate the Out-of-range Limits

Use the following equation to compute low and high out-of-range
limits.

Ladder Logic

We present two examples for programming the processor.

The first example uses standard math instructions available in any
SLC 500 processor. This ladder logic prevents a processor fault by
unlatching the mathematical overflow bit S2:5/0 before the end of the
scan.

The second example uses the scaling instruction (SCL) available in
SLC 5/02 (and later) processors. The rate parameter is calculated by
multiplying the slope by 10,000. If the slope exceeds 3.2767, you
cannot use the SCL instruction.

Scaled value = (input value x slope) + offset

Slope = (scaled max – scaled min) / (input max – input min)

Offset = scaled min – (input min x slope)

(500 – 100) / (4095 – 0) = 400/4095 = 0.0977

(100 – (0 x [400/4095]) = 100

Scaled value = (input value x [0.0977]) + 100

Input value = (scaled value – offset) / slope

low limit: (275 – 100) / (0.0977) 1750 counts

~

high limit: (300 – 100) / (0.0977) 2750 counts

~

rate = (400/4095) x 10,000 = 977