Publication 1746-UM009B-EN-P - September 2007

Calibrate the Module 63

These addresses are used in the example program.
(Each channel requires its own program and separate addresses.)

Compute values required for the calibration program as follows:

Example Program Addresses

Bit or Value

Address

Cal_Lo

I:1.0/0 and N10:0/0 (You set these bits in step 3.)

Cal_Hi

I:1.0/1 and N10:0/1 (You set these bits in step 4.)

Calibrate

I:1.0/2 and N10:0/2 (You set these bits in step 5.)

Convert Enable

N10:10/4 (Runtime enable)

Analog_In

I:2.0

Lo_Value

N10:1

Hi_Value

N10:2

Scale_Hi

N10:3

Scale_Lo

N10:4

Scale_Span

N10:7

Span

N10:9

Slope_x10K

N10:18

Offset

N10:21

Analog Scale

N10:22

Scaled value = (input value x slope) + offset

Slope = (scaled max. – scaled min.) / (input max. – input min.)

Offset = scaled min. – (input min. x slope)

= (2047 – 409) / (2055 – 400)

1

= 1638 / 1655 = .9897

= 409 – (400 x .9897) = 409 – 395.88 = 13.12

1

The values of 2055 and 400 are from the calibration procedure steps 3 and 4, respectively.

20 mA = 2047
(scale high)

Scaled
Value

Input Value

2055
(High Input)

400

(Low Input)

4 mA = 409
(scale low)