Configure the Modules with RSLogix 5000 Software Chapter 7

An example for a Flow Meter might be:

• PV - Primary Variable. Flow Rate in Liters per Minute.
• SV - Secondary Variable. Process Temperature in °C.
• TV - Third or Tertiary Variable. Product Density in Grams per Cubic

Centimeter.

• FV - Fourth or Quaternary Variable

An example for a Valve Positioner might be:

• PV - Primary Variable. Commanded position in %.
• SV - Secondary Variable. Actual position in %.
• TV - Third or Tertiary Variable. Air Pressure in PSI.
• FV - Fourth or Quaternary Variable. Loop current in mA.

In addition to the measurement value, HART devices can provide status
information that indicates the quality of the measurement.

For example, if a valve positioner cannot open any further, it should set its
HART.ChxSVStatus to 2#11100000 to indicate that the actual position value in
the SV is Good (accurately measured) but is the subject of a High Limit. This
status information can be used for windup control in PID loops and for other
diagnostic purposes.

Device Family Specific Status

More Device Variable Status Available

Limit Status
11 Constant
01 Low Limited
10 High Limited
00 Not Limited

Process Data Status
11 Good
01 Poor Accuracy
10 Manual/Fixed
00 Bad