Rockwell Automation Publication 1756-UM533C-EN-P - February 2011

Chapter 4

1756-IF8H HART Analog Input Module

For devices powered by individual supplies, when the ground potential of the
supplies is expected to differ, Differential mode is recommended. This prevents
ground loop currents from flowing between the supplies. However, the potential
difference allowable between the supplies must remain within the specified
limits.

Figure 8 - Power Supplies with Isolated Grounds

Some devices, such as AC powered four-wire devices, are recommended to be
used in Differential mode only. It is best if differential and

single-ended

input

types are not combined onto the same terminal block, that is, all should be
single-ended or all should be differential.

Circuit Diagrams

This section shows the 1756-IF8H module’s input circuit diagrams.

Figure 9 -

Simplified 1756-IF8H Current Input Circuit

Power Supply 1

HART
Device 1

HART
Device 2

Power Supply 2

Ground wire isolated
from each other

IN0+

IRTN-0

IRTN-1

RTN

IN1+

IN0-

IN1-

+

-

+

-

The low end of the terminal block pins are now isolated from each other
and the inputs can be configured as true differential inputs as long as the
voltage difference between them does not exceed 7V.

32140-M

0.01

μF

Analog to
Digital
Converter

22 K

Ω

10 M

Ω

RTN

RTN

RTN

RTN

-15 V

Jumper

+

-

0.01

μF

22 K

Ω

10 M

Ω

249

Ω

1/4 Watt

INO+

IRTN-O

INO-

+15 V

Differential
Current
Input

i