Unlatch Alarms and Reconfigure Modules By Using Ladder Logic Chapter 10

The Configuration tab provides information on what module service to perform
and where to perform it. For example, you must use this dialog to unlatch high
high alarms (module service) on channel 0 of a module (where to perform
service).

You select a service type by clicking the drop-down. A list of available services
includes to unlatch high high, high, low low, low, low, ramp, and rate alarms.

The Communication tab provides information on the path of the message
instruction. For example, the slot number of a 1756-IF6I module distinguishes
exactly for which module a message is designated.

.

IMPORTANT

Click Browse to see a list of the I/O modules in the system.

You choose a path when you choose a module from the list.

You must name an I/O module during initial module configuration to
choose a path for your message instruction.