Appendix A Tag Definitions

Ch0HAlarm

BOOL

Ch0Status.2
Ch0Data > Ch0HAlarmLimit
If Ch0Config.ProcessAlarmLatch is set, this alarm remains set until it is unlatched

Ch0LAlarm

BOOL

Ch0Status.3
Ch0Data < Ch0LAlarmLimit
If Ch0Config.ProcessAlarmLatch is set, this alarm remains set until it is unlatched.

Ch0RateAlarm

BOOL

Ch0Status.4
Ch0Data changing faster than Ch0RateAlarmLimit.
Both positive and negative changes can cause this alarm.
If Ch0Config.RateAlarmLatch is set, this alarm remains set until it is unlatched.

Ch0Overrange

BOOL

Ch0Status.5
Analog signal is greater than or equal to the maximum detectable signal. Because the signal cannot
be measured, it may be significantly above the maximum value.

Ch0Underrange

BOOL

Ch0Status.6
Analog signal is less than or equal to the minimum detectable signal. Because the signal cannot be
measured, it may be significantly below the minimum value.

Ch0CalFault

BOOL

Ch0Status.7
Set if an error occurs during calibration for Channel x, causing a bad calibration. Also sets CalFault.

Ch1Status

SINT

Binary

Indicates various alarms on the analog signal. Also sets Ch1Fault.

Ch2Status

SINT

Binary

Indicates various alarms on the analog signal. Also sets Ch2Fault.

Ch3Status

SINT

Binary

Indicates various alarms on the analog signal. Also sets Ch3Fault.

Ch4Status

SINT

Binary

Indicates various alarms on the analog signal. Also sets Ch4Fault.

Ch5Status

SINT

Binary

Indicates various alarms on the analog signal. Also sets Ch5Fault.

Ch6Status

SINT

Binary

Indicates various alarms on the analog signal. Also sets Ch6Fault.

Ch7Status

SINT

Binary

Indicates various alarms on the analog signal. Also sets Ch7Fault.

Ch0Data

REAL

Float

Value of analog signal on Channel 0 after conversion to engineering units.

Ch1Data

REAL

Float

Value of analog signal on Channel 1 after conversion to engineering units.

Ch2Data

REAL

Float

Value of analog signal on Channel 2 after conversion to engineering units.

Ch3Data

REAL

Float

Value of analog signal on Channel 3 after conversion to engineering units.

Ch4Data

REAL

Float

Value of analog signal on Channel 4 after conversion to engineering units.

Ch5Data

REAL

Float

Value of analog signal on Channel 5 after conversion to engineering units.

Ch6Data

REAL

Float

Value of analog signal on Channel 6 after conversion to engineering units.

Ch7Data

REAL

Float

Value of analog signal on Channel 7 after conversion to engineering units.

CSTTimestamp

DINT[2]

Hex

Timestamp taken at the time the input data was sampled in terms of coordinated system time,
which is a 64-bit value in microseconds coordinated across the modules in the 1756 backplane.

RollingTimestamp

INT

Decimal

Timestamp taken at the time the input data was sampled in millisecond resolution.

HART

AB:1756_IF8H_HARTData:I:1, Contains HART field device health and dynamic process variables.

Ch0DeviceStatus

AB:1756_IF8H_HARTStatus_Struct:I:1, Channel 0 HART Device status info.

Init

BOOL

Searching for or Initializing HART device.
If this is 0 and Fail is 1, then HART is not enabled on this channel.
If both are 1, then 1756-IF8H is sending out HART messages attempting to establish communication
with a HART device.

Fail

BOOL

HART communication failure or device not found or HART not enabled.
If this bit is 1, none of the other data in the HART part of the input tag are valid.
(HART.PVStatus will be set to 0 to also indicate this).

MsgReady

BOOL

Pass-through message reply is ready for query service.

Table 60 - Analog and HART PV (AB:1756_IF8H_HARTPV:I:1)