1756-IF16H HART Analog Input Module Chapter 5

Module Filter

The module filter attenuates the input signal beginning at the specified
frequency. This feature is applied on a module-wide basis, affecting all channels.

The module attenuates the selected frequency by approximately -3 dB or 0.707 of
the applied amplitude.

An input signal with frequencies above the selected frequency is attenuated more
while frequencies below the selection receive no attenuation.

In addition to frequency rejection, a by-product of the filter selection is the
minimum sample rate (RTS) that is available. For example, the 1000 Hz selection
does not attenuate any frequencies less than 1000 Hz, and provides for sampling
of all 16 channels within 18 ms. The 15 Hz selection attenuates all frequencies
above 15 Hz and provides only for sampling all 16 channels within 328 ms.

Use the following table to choose a module filter setting.

IMPORTANT

Do not use the 1000 Hz module filter with HART instruments.

IMPORTANT

60 Hz is the default setting for the module filter. This setting provides
approximately 3 dB of attenuation of a 60 Hz input.

Table 10 - Module Filter Selections with Associated Performance Data

Module Filter
Selection (-3dB)

(1)

(1) Worst case settling time to 100% of a step change is double the real time sample time.

15 Hz

20 Hz

50 Hz

60 Hz

100 Hz

250 Hz

1000 Hz

Minimum Sample Time
(RTS)

328 ms

275 ms

115 ms

115 ms

61 ms

25 ms

11 ms

Effective Resolution

18 bits

18 bits

17 bits

17 bits

16 bits

16 bits

15 bits

0.08

μA 0.08 μA 0.16 μA 0.16 μA 0.32 μA 0.32 μA 0.64 μA

50 Hz Rejection

74 dB

48 dB

6 dB

6 dB

1 dB

0.1 dB

N/A

60 Hz Rejection

74 dB

97 dB

9 dB

9 dB

2 dB

0.2 dB

N/A

.707

60 Hz