43

ControlLogix Module Operation Chapter 3

In the example below, the real time sample value is 100 ms and the requested
packet interval value is 25 ms. Only every fourth multicast from the module
contains updated channel data.

Trigger Event Tasks

When configured to do so, ControlLogix analog input modules can trigger an
event task. The event task offers ControlLogix controller users a task that
executes a section of logic immediately when an event (receipt of new data)
occurs.

Your ControlLogix analog I/O module can trigger event tasks every real time
sample, after the module has sampled and multicast its data. Events tasks are
useful for synchronizing process variable (PV) samples and proportional integral
derivative (PID) calculations.

Real Time Sample (RTS)
100 ms - Updated data

Requested Packet
Interval
25 ms - Same input data
as the previous RTS

25

50

75

100 125 150 175

200 225 250 275

300 325 350 375

400

Time (ms)

40946

IMPORTANT

ControlLogix analog I/O modules can trigger event tasks at
every real time sample, but not at the requested packet
interval. For example, in the figure, an event task can be only
triggered every 100 ms.